Fiber Optic Cables
Patch Cords
Quick Reference
APC and UPC connectors cannot and should not be mated. Not only does mating cause poor performance because the fiber cores will not touch, but it can also destroy both connectors. The last thing you want to do is cause permanent transceiver damage, especially on higher-cost single-mode equipment.
Detailed Information
The buffer or jacket on patchcords is often color-coded to indicate the type of fiber used. The strain relief "boot" that protects the fiber from bending at a connector is color-coded to indicate the type of connection. Connectors with a plastic shell (such as SC connectors) typically use a color-coded shell. Standard color codings for jackets (or buffers) and boots (or connector shells) are shown below:
Color | Meaning | 1Gb | 10Gb | 40Gb | 100Gb | 400Gb | |
---|---|---|---|---|---|---|---|
Yellow | OS1/OS2 single-mode optical fiber, 9/125 μm | 100 km | 40 km | 40 km | 40 km | ||
Lime green | OM5 multi-mode optical fiber, laser-optimized, 50/125 µm | 1100 m | 550 m | 150 m | 150 m | 150 m | |
Aqua | OM3/OM4 multi-mode optical fiber, laser-optimized, 50/125 µm | 1000 m / 1100 km | 300 m / 550 m | 100 m / 150 m | 100 m / 150 m | 150 m | |
Magenta | OM3/OM4 multi-mode optical fiber, laser-optimized, 50/125 µm (12+ strands) | 1000 m / 1100 km | 300 m / 550 m | 100 m / 150 m | 100 m / 150 m | 150 m | |
Orange | OM1/OM2 multi-mode optical fiber, 62.5/125 μm | 300 m / 600 m | 30 m / 150 m | n/a | n/a | n/a | |
Grey | Outdated color code for multi-mode optical fiber |
Color | Meaning | Comment | |
---|---|---|---|
Blue | Ultra Physical Contact (UPC), 0° | With UPC connectors, insertion loss is lower than with APC. Achieving low insertion loss is typically easier with UPC connectors due to less air gaps than APC connectors. Consequently, return loss is higher with UPC because reflected light is reflected straight back toward the light source. | |
Green | Angled Physical Contact (APC), 8° | The angled endface of the APC connector causes reflected light to reflect at an angle into the cladding vs. straight back toward the source. This is ideal for applications that are sensitive to return loss. Consequently, insertion loss is higher with APC than with UPC. Remember, return loss is different than insertion loss (the amount of optical power lost through a connector or cable length). | |
Grey | Physical Contact (PC), 0° | Multimode fiber connectors | |
Beige |
APC and UPC connectors cannot and should not be mated. Not only does mating cause poor performance because the fiber cores will not touch, but it can also destroy both connectors. The last thing you want to do is cause permanent transceiver damage, especially on higher-cost single-mode equipment.
Single-Mode
A typical single-mode optical fiber has a core diameter between 8 and 10.5 µm and a cladding diameter of 125 µm. There are a number of special types of single-mode optical fiber which have been chemically or physically altered to give special properties, such as dispersion-shifted fiber and nonzero dispersion-shifted fiber. Data rates are limited by polarization mode dispersion and chromatic dispersion.
Multi-Mode
The main difference between multi-mode and single-mode optical fiber is that the former has much larger core diameter, typically 50–100 micrometers; much larger than the wavelength of the light carried in it. Because of the large core and also the possibility of large numerical aperture, multi-mode fiber has higher "light-gathering" capacity than single-mode fiber. In practical terms, the larger core size simplifies connections and also allows the use of lower-cost electronics such as light-emitting diodes (LEDs) and vertical-cavity surface-emitting lasers (VCSELs) which operate at the 850 nm and 1300 nm wavelength (single-mode fibers used in telecommunications typically operate at 1310 or 1550 nm). However, compared to single-mode fibers, the multi-mode fiber bandwidth–distance product limit is lower.
MTP/MPO
MPO (Multi-fiber Push On) cables are terminated with MPO connectors at either end. MPO fiber connectors are designed to provide multi-fiber connectivity in one connector to support high bandwidth and high-density cabling system applications. MPO connector is compliant with the IEC 61754-7 standard and the U.S. TIA-604-5 standard. At present, MPO connectors are typically available with 8, 12, 16 or 24 fibers for common data center and LAN applications, and 32, 48, 60, 72 fiber counts are also possible in large scale optical switches for specialty super high- density multi-fiber arrays.
Pinning and Polarity
Pinned = Male
Unpinned = Female
To Do: Finish this section...
Differences MTP vs MPO®
In short, MTP® is just a brand of MPO cable; the Kleenex, if you will. You can use the terms "MPO" and "MTP" interchangeably. MTP® cables, short for "MulTi-fiber Pull-off", are equipped with MTP® fiber connectors at either end. MTP® connector is a trademark by US Conec for a version of the MPO connector with improved specifications. So MTP® connectors are fully compliant with all generic MPO connectors and can interconnect directly with other MPO based infrastructures. However, the MTP® connector is a multiple engineered product enhancement to improve mechanical and optical performance when compared to generic MPO connectors.
Helpful Links
http://www.fiberopticshare.com/introduction-polarity-methods-mtpmpo-systems.html
https://www.fiberopticshare.com/understanding-mtpmpo-polarity-methods-parallel-signals.html
https://www.servethehome.com/mpo-mtp-male-and-female-connector-differences/
https://www.blackbox.com/en-au/insights/black-box-explains/fibre-optic-cable/mpo-pinning-methods